[8PWR] Sensors Plugin

Sensors 1-Wire

Sensors 1-Wire (Temperature 1-wire, (THS), 2m and Humidity sensor 1-wire) connected to the connectors 1W plugs RJ12, allowed to use extension cords or splitters. Maximum cable length 1-Wire network is limited to 50 meters.

Sensors of Dry Contact Type

Dry contact sensors are door opening sensors, buttons and other sensors, with a mechanism of work based on opening/closing a conductor. A sensor is connected with two wires to an IO line of a device according to the table (an order of plugging wires does not matter).

Sensor Flex

NetPing 8/PWR-220 v4/SMS Terminal

First wire

One of IO lines – 1/2/3/4

Second wire

G

Important! Sensors of a dry contact type, a supply voltage sensor, a leakage sensor, and others are plugged to IO lines of a device. You can plug any four sensors out of this set.

Important! A corresponding IO line should be set to an input mode in settings of a device.

A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of flat cable extenders of RC-4 sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section of 0,4 mm2. Maximum allowable length of a flat cable is 100 m.

Leakage Sensors

A leakage sensor is connected by a four-wire line according to the table.

Sensor Flex

NetPing 8/PWR-220 v4/SMS Terminal

Green

One of IO lines – 1/2/3/4

Yellow (White)

G

Red

+

Black

G

Important! Sensors of a dry contact type, a supply voltage sensor, a leakage sensor, and others are plugged to IO lines of a device. You can plug any four sensors out of this set.

Important! A corresponding IO line should be set to an input mode in settings of a device.

A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of flat cable extenders of RC-4 sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section of 0,4 mm2. Maximum allowable length of a flat cable is 100 m.

Supply Voltage Sensor

supply voltage sensor is plugged by a two-wire line according to the table. An order of plugging wires does not matter.

Sensor Flex

NetPing 8/PWR-220 v4/SMS Terminal

First wire

One of IO lines – 1/2/3/4

Second wire

G

Important! Sensors of a dry contact type, a supply voltage sensor, a leakage sensor, and others are plugged to IO lines of a device. You can plug any four sensors out of this set.

Important! A corresponding IO line should be set to an input mode in settings of a device.

A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of flat cable extenders of RC-4 sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section of 0,4 mm2. Maximum allowable length of a flat cable is 100 m.

IR Transceiver IRC-TR v2

IR transceiver is plugged by a four-wire line according to the table:

Sensor Flex

NetPing 8/PWR-220 v4/SMS Terminal 

Labeled wire (red)

C

Second wire after a labeled one

D

Third wire after a labeled one

+

Fourth wire after a labeled one

G

A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of flat cable extenders of RC-4 sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section of 0,4 mm2. Maximum allowable length of a flat cable is 100 m.

Plugging NetPing AC/DIN Sockets

When plugging a socket to a device, all wires are used except for a brown one. There is a need to switch an IO line, to which a NetPing AC/DIN socket is connected, to the status "output". When a status of an IO line is logic 0, the socket will have 220V, and a load will be turned on. When a status of an IO line is logic 1, a socket will be cut off power, and a load will be turned off.

Important! A brown wire is not used and must stay unplugged!

Sensor Flex

NetPing 8/PWR-220 v4/SMS Terminal

Red

+

Black

G

Blue (Green)

Одна из IO линий – 1/2/3/4


A relay with normally closed contacts is used to switch load in NetPing AC/DIN. This means if a control wire is not plugged anywhere, 220V will be in the socket and a load will be switched on.

A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of flat cable extenders of RC-4 sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section of 0,4 mm2. Maximum allowable length of a flat cable is 100 m.