[ENG] 12.7. [DKSF 48.5 IU] What Kinds of SMS Notifications Can This Device Send?

Syntax of SMS Notifications

SMS Notifications look like:

np_name (q) information 

where:

np_name — is the name of the device for the identification of SMS messages up to 30 Latic characters. The name is set on the page "SETUP" of the device`s web interface. If the name of the device is not set, the "NETPING" name is used instead of it. 

 is the sequence number of messages. The number is nonvolatile. It does not reset when the power is switched off.  It is needed for the registration of the missed (lost) messages.

Information - is the informative part of SMS messages.

Informative part of SMS messages

 A messages from the temperature sensor

TEMP.SENSOR j "label" IS FAILED — temperature sensor failure (the sensor stopped responding to the poll);

TEMP.SENSOR "label" IN SAFE RANGE (t1 TO t2), NOW tC — the readings have returned to the safe range; 

TEMP.SENSOR "label" BELOW SAFE RANGE (t1 TO t2), NOW tC — the temperature goes below the safe range:

TEMP.SENSOR j "label" ABOVE SAFE RANGE (t1 TO t2), NOW tC  -  the temperature goes above the safe range;

where:

  • j — number of a temperature sensor, 1...8.
  • label — a label of a temperature sensor which is set in the entry field “Memo” on the page “TEMPERATURE” of the device`s web-interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS.
  • t1, t2 —  the thresholds of normal temperature range, °C.
  • — current temperature, °C .

Messages from Humidity Sensor

RHj FAILEDhumidity sensor failure (the sensor stopped responding to the poll)

RHj ht (above the safe range ht1...ht2) —  the readings of humidity and temperature are above the safe range

RHj ht (below the safe range ht1...ht2) — the readings of humidity and temperature are below the safe range

RHj ht (in the safe range ht1...ht2) — the reading of the humidity are in the safe range.

RHj is OK, h status, t status — the connection with the sensor is restored

 где:

  • — number of temperature sensor, 1...4.
  • ht — relative humidity or temperature
  • ht1, ht2 — the thresholds of normal relative humidity range and temperature
  • h — relative humidity;
  • t — temperature;
  • status — the status of readings:"in the safe range", "below the safe range", "above the safe range"

Messages about the che change in status of a smoke sensor

SMOKE SENS.n "label" — status

where:

  • n — number of the smoke sensor, 1...4;
  • label  - a label of a temperature sensor which is set in the entry field “Memo” on the page “SMOKE” of the device`s web-interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS. The Cyrillic symbols are depicted with the sign «?»;
  • status — the smoke sensor status, possible values: «OK», «ALARM!», «SWITCHED OFF», «FAILED».

 Messages from a buil-in relay

RELAY j "label" ORDERED TO SWITCH mode VIA src — a command for changing the relay status has been received

RELAY j "label" SWITCHED mode —the relay is switched in the state mode

RELAY j "label" RESET VIA/BY src — the relay has received the command for reset

where:

  • j —the number of relay, 1...8;
  • label — a relay label is set in the “Memo” entry field on the “AC OUTLETS” page of the device’s web interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS.
  • mode — the operationg mode of the relay: «on» или «off»;
  • src — the command sources: «WEB», «SNMP», «SMS», «SCHELUDE», «WATCHGOD», «LOGIC».

Messages from the "Watchdog"

WDOG j "label" RESET — The reset of the relay began by the watchdog.

WDOG j "label" CEASED AFTER n FAILED RESETS —  the operating of the "Watchdog" ceased and failed resets

WDOG j "label" GOT REPLY, RESTORED —  the operating of the "Watchdog" is restored

where:

  • j — the number of relay, 1...8;
  • label — a relay label is set in the “Memo” entry field on the “AC OUTLETS” page of the device’s web interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS.
  • n — the number of unsuccessful resets before the watchdog stops working, it is configured in the watchdog notification settings dialogue 

Messages about the status change of the Ethernet ports of the device

ETHERNET LINK STATUS: 1 UP|DOWN, 2 UP/DOWN

 A message about the recovery/failure of the communication with the specified IP address  (the "Pinger" module on the "SMS" page):

PINGER STATUS: OK|FAILED (IP/HOST)

where:

IP/HOST —  IP address of the checked address/host

Messages from power inputs:

AC INPUT j "label": status

where:

j —  power input number, 1 or 2;

  • label — a relay label is set in the “Memo” entry field on the “AC OUTLETS” page of the device’s web interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS.

status —  the availabity of voltage in the inpu t«OK» or «FAILED».

Message from the groups of outlets

OUTLETS gg SWITCHED TO AC INPUT i "label"

where:

  • gg — a group of the input outlets, 1...4 or 5...8;
  • i — power input number, 1 или 2;
  • label — label is set in the “Memo” entry field on the “AC OUTLETS” page of the device’s web interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in the SMS.

Messages from IO Lines

IOn=0|1 "label" "transcript"

where:

  • — IO line number, 1...4;
  • label —a label is set in the “Memo” entry field on the “DISCRETE IO” page of the device’s web interface. If the label is not specified (empty), then it is not included in the SMS.
  • transcript — the decryption of the logical level of the IO line is set in the pop up dialog for setting notifications from IO lines on the "DISCRETE IO" page of the device’s web interface. If the decryption is not set (empty), then it is not included in the SMS.

Custom Notifications

In addition to notifications with fixed text, starting with the firmware version DKSF 48.5.3, it is possible to send custom “Custom notifications”, in the text of which some SNMP variables can be included. More details in the section [ENG] 13. [DKSF 48.5 IU] Device Support for Custom Notifications