[ENG] 10.5. [DKSF 54.3 IU] How to Power On and Reset 1-Wire Smoke Sensors?

Smoke sensors are powered on or reset on the page «SMOKE» of a device web interface:

Resetting 1-Wire smoke sensors in a NetPing 4PWR-220 v4SMS device

A checkbox «Power» allows supplying voltage to smoke sensors. On default: checkbox is not checked

Clicking the button «Reset» on a web page removes power from a current loop that is connected to a sensor, for 10 seconds.

The same it is possible to control power and reset sensors using an SNMP v1 protocol by setting OID values using a command Set:

OID

Name

Type

Access

Description

.1.3.6.1.4.1.25728.8200.1.1.3.n

npSmokePower.n

Integer

READ/WRITE

Controlling a power supply of a 1-wire smoke sensor,

where

n – is a number of a sensor:

0 – Off

1 – On

.1.3.6.1.4.1.25728.8200.1.1.4.n

npSmokeReset.n

Integer

READ/WRITE

OID for forced short-term switching off a 1-wire smoke sensor,

where

n – is a number of a sensor.

Write the number «1» for switching a channel off for 10 seconds.