[ENG] 7.5. [DKSF 53/203.1 IU] I Want to Configure Sending Notifications When a Logic Level of an Input-Output Line Is Changed. How to Do This?

Notifications on changing a logic level of an IO line are configured at the page «DISCRETE IO» of a device web interface:

When clicking the button «Setup» a menu of settings appears for configuring sending notifications of the next types: Log, Syslog, E-mail, SMS (in devices with an embedded GSM modem) and SNMP Trap, as well as encoding numeric values of a current level of an IO line:

where:

Front (level change 0->1) – is a checkbox, when checked a device will send notifications if a status of an IO line is changed from «0» to «1»On default: checkbox is not checked

Decay (level change 1->0) – is a checkbox, when checked a device will send notifications if a status of an IO line is changed from «1» to «0»On default: checkbox is not checked

Include in Summary Report – is a checkbox, when checked a device will send reports about a status of an IO line via e-mail and/or SMS. Time for sending reports is configured at the pages «SMS» and «E-MAIL». On default: checkbox is not checked

Logic level Logic 1  a clear and understandable description of a numeric value of a level «Logic 1» of an IO line is set. This decoding will be displayed in the field «Legend» at the page «INPUT-OUTPUT» of a device web interface and will be added to SNMP TRAP notifications.

Logic level Logic 0 – a clear and understandable description of a numeric value of a level «Logic 0» of an IO line is setThis decoding will be displayed in the field «Legend» at the page «INPUT-OUTPUT» of a device web interface and will be added to SNMP TRAP notifications.

After setting all necessary parameters click the button «Apply changes».