[ENG] 10.6. [DKSF 52/202.10 IU] Reset Signal and Initial Statuses of Outputs

When firmware starts operating or when the button «Reset» is clicked at the page «LOGIC» of a device web interface, the outputs controlled by logic are returned to the initial status. On default, this status is «off» or «logic 0». Another status can be set using the rule at the page «LOGIC», which uses reset signal «RESET» as an input.

After the firmware restarts, a logic configuration is saved or the button «Reset» is clicked at the page of a logic, there is a pause for 5 seconds. Then, after these 5 seconds the reset signal «RESET» is activated.

A rule with a condition «If RESET = logic 1» is activated 5 seconds after a reset.
A rule with a condition «If RESET = logic 0» is activated 10 seconds after a reset.
A rule with a condition «While RESET = logic 1» is active for 5 seconds 5 seconds after a pause.
A rule with a condition «While RESET = logic 0» is always active except for 5 seconds of resetting period.

Therefore, it is possible to form a 5-second external reset pulse on one or several outputs or provide a correct sequence of power supply to external devices.